{"id":2853,"date":"2024-08-25T19:40:01","date_gmt":"2024-08-25T19:40:01","guid":{"rendered":"https:\/\/workhouse.sweetdishy.com\/?p=2853"},"modified":"2024-08-25T19:40:02","modified_gmt":"2024-08-25T19:40:02","slug":"transformer-on-no-load","status":"publish","type":"post","link":"https:\/\/workhouse.sweetdishy.com\/index.php\/2024\/08\/25\/transformer-on-no-load\/","title":{"rendered":"TRANSFORMER ON NO-LOAD"},"content":{"rendered":"\n<p id=\"para-206\">A transformer is said to be on no-load when secondary winding is open circuited and the secondary current&nbsp;<em>I<\/em><sub>2&nbsp;<\/sub>is zero. In this case, neither the secondary winding has any effect on the magnetic flux in the core nor it has any effect on the primary current.<\/p>\n\n\n\n<p id=\"para-207\">In actual transformer, the losses cannot be neglected. Therefore, if transformer is on no-load, a small current&nbsp;<em>I<\/em><sub>0<\/sub>&nbsp;(usually 2% to 10% of the rated value) called exciting current is drawn by the primary. This current has to supply the iron losses (hysteresis and eddy current losses) in the core&nbsp;<a><\/a>and a very small amount of copper loss in the primary (the primary copper losses are so small as compared to core losses that they are generally neglected moreover secondary copper losses are zero as&nbsp;<em>I<\/em><sub>2<\/sub>&nbsp;is zero).<\/p>\n\n\n\n<p id=\"para-208\">Therefore, current\u00a0<em>I<\/em><sub>o\u00a0<\/sub>lags behind the voltage vector\u00a0<em>V<\/em><sub>1\u00a0<\/sub>by an angle\u00a0<em>\u0278<\/em><sub>0<\/sub>\u00a0(called hysteresis angle of advance) which is less than 90\u00b0, as shown in\u00a0Figure 10.13(b). The angle of lag depends upon the losses in the transformer. The no-load current\u00a0<em>I<\/em><sub>0<\/sub>\u00a0has two components:<\/p>\n\n\n\n<ol class=\"wp-block-list\" id=\"ol-012\">\n<li>One,&nbsp;<em>I<\/em><sub>w<\/sub>&nbsp;in phase with the applied voltage&nbsp;<em>V<\/em><sub>1<\/sub>, called active or working component. It supplies the iron losses and a small primary copper losses.<\/li>\n\n\n\n<li>The other,&nbsp;<em>I<\/em><sub>mag<\/sub>&nbsp;in quadrature with the applied voltage&nbsp;<em>V<\/em><sub>1<\/sub>, called reactive of magnetizing component. It produces flux in the core and does not consume any power.<\/li>\n<\/ol>\n\n\n\n<p id=\"para-209\">From phasor (vector) diagram shown in&nbsp;<a href=\"https:\/\/learning.oreilly.com\/library\/view\/basic-electrical-engineering\/9789332558311\/xhtml\/Chapter010.xhtml#Fig_10-13\">Figure 10.13(b)<\/a>.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page515_1.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-210\"><strong>Fig. 10.13<\/strong>&nbsp;&nbsp;(a) Transformer on no-load (b) Phasor diagram of transformer at no-load<\/p>\n\n\n\n<p id=\"para-211\">Working component,<\/p>\n\n\n\n<p id=\"para-212\">&nbsp;<\/p>\n\n\n\n<p><em>I<\/em><sub>w<\/sub><em>&nbsp;= I<\/em><sub>0<\/sub>&nbsp;cos<em>&nbsp;\u0278<\/em><sub>0<\/sub><\/p>\n\n\n\n<p id=\"para-213\">Magnetizing component,<\/p>\n\n\n\n<p id=\"para-214\">&nbsp;<\/p>\n\n\n\n<p><em>I<\/em><sub>mag<\/sub><em>&nbsp;= I<\/em><sub>0<\/sub>&nbsp;sin&nbsp;<em>\u0278<\/em><sub>0<\/sub><\/p>\n\n\n\n<p id=\"para-215\">No-load current,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page515_2.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-216\">Primary p.f. at no-load,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page515_3.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-217\">No-load power input,<\/p>\n\n\n\n<p id=\"para-218\">&nbsp;<\/p>\n\n\n\n<p><em>P<\/em><sub>0<\/sub>&nbsp;=&nbsp;<em>V<\/em><sub>1<\/sub><em>I<\/em><sub>0<\/sub>&nbsp;cos&nbsp;<em>\u0278<\/em><sub>0<\/sub><\/p>\n\n\n\n<p id=\"para-219\">Exciting resistance,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page515_4.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-220\">Exciting reactance,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page515_5.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-221\">The equivalent circuit of a transformer at no-load is shown in\u00a0Figure 10.14. Here,\u00a0<em>R<\/em><sub>0\u00a0<\/sub>represents the exciting resistance of the transformer that carries power loss component of no-load current, that is,\u00a0<em>I<\/em><sub>w\u00a0<\/sub>used to meet with the no-load losses in the transformer, whereas\u00a0<em>X<\/em><sub>0\u00a0<\/sub>represents the exciting reactance of the transformer that carries watt-less component of no-load current, that is,<em>\u00a0I<\/em><sub>mag\u00a0<\/sub>used to set up magnetic field in the core.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page516_1.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-222\"><strong>Fig. 10.14<\/strong>&nbsp;&nbsp;Equivalent circuit of a transformer at no-load<\/p>\n\n\n\n<p id=\"para-223\"><strong>Example 10.8<\/strong><\/p>\n\n\n\n<p id=\"para-224\">A 230\/110 V single-phase transformer has a core loss of 100 W. If the input under no-load condition is 400 VA, find core loss current, magnetizing current, and no-load power factor angle.<\/p>\n\n\n\n<p id=\"para-225\"><em>Solution:<\/em><\/p>\n\n\n\n<p id=\"para-226\">Here,<\/p>\n\n\n\n<p id=\"para-227\">&nbsp;<\/p>\n\n\n\n<p><em>V<\/em><sub>1<\/sub>&nbsp;= 230 V;&nbsp;<em>V<\/em><sub>2<\/sub>&nbsp;= 110 V;&nbsp;<em>V<\/em><sub>2<\/sub>&nbsp;= 110 V;&nbsp;<em>P<\/em><sub>i<\/sub>&nbsp;= 100 W<\/p>\n\n\n\n<p id=\"para-228\">Input at no-load = 400 VA<\/p>\n\n\n\n<p id=\"para-229\">That is,<\/p>\n\n\n\n<p id=\"para-230\">&nbsp;<\/p>\n\n\n\n<p><em>V<\/em><sub>1<\/sub><em>I<\/em><sub>0<\/sub>&nbsp;= 400<\/p>\n\n\n\n<p id=\"para-231\">or no-load current<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page516_2.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-232\">Core loss current,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page516_3.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-233\">Magnetizing current,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page516_4.png\" alt=\"img\" width=\"473\" height=\"46\"><\/p>\n\n\n\n<p id=\"para-234\">No-load power factor,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page516_5.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-235\">No-load power factor angle,<\/p>\n\n\n\n<p><em>\u0278<\/em><sub>0<\/sub>&nbsp;= cos<sup>\u22121<\/sup>&nbsp;0.25 = 75.52\u00b0<\/p>\n\n\n\n<p id=\"para-236\"><strong>Example 10.9<\/strong><\/p>\n\n\n\n<p id=\"para-237\">A single-phase, 50 kVA, 2300\/230 V, 50 Hz transformer is connected to 230 V supply on the secondary side, the primary being open. The meter indicates the following readings:<em>\u2013<\/em><\/p>\n\n\n\n<p id=\"para-238\">Power = 230 W<\/p>\n\n\n\n<p id=\"para-239\">Voltage = 230 V<\/p>\n\n\n\n<p id=\"para-240\">Current = 6.5 A<\/p>\n\n\n\n<p id=\"para-241\">Find (i) core loss, (ii) loss component of the current, and (iii) magnetizing current. Draw the phasor diagram for this condition.<\/p>\n\n\n\n<p id=\"para-242\"><em>Solution:<\/em><\/p>\n\n\n\n<p id=\"para-243\">Power input at no-load,&nbsp;<em>P<\/em><sub>0<\/sub>&nbsp;= 230 W<\/p>\n\n\n\n<p id=\"para-244\"><a><\/a>Supply voltage,<\/p>\n\n\n\n<p id=\"para-245\">&nbsp;<\/p>\n\n\n\n<p><em>V<\/em><sub>1&nbsp;<\/sub>= 230 V<\/p>\n\n\n\n<p id=\"para-246\">Current at no-load,<\/p>\n\n\n\n<p id=\"para-247\">&nbsp;<\/p>\n\n\n\n<p><em>I<\/em><sub>0&nbsp;<\/sub>= 6.5 A<\/p>\n\n\n\n<ol class=\"wp-block-list\" id=\"ol-013\">\n<li>Since low-voltage winding resistance is not given, the copper losses cannot be separated, and therefore, whole of the power input will represent the iron or core losses.\u2234 Core loss = 230 W<\/li>\n\n\n\n<li>Using relation&nbsp;<em>P<\/em><sub>0<\/sub>&nbsp;=&nbsp;<em>V<\/em><sub>1<\/sub><em>J<\/em><sub>0<\/sub>&nbsp;cos<em>\u0278<\/em><sub>0<\/sub>&nbsp;=&nbsp;<em>V<\/em><sub>1<\/sub><em>I<\/em><sub>w<\/sub>Loss component of current,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page517_1.png\" alt=\"img\" width=\"218\" height=\"67\"><\/li>\n\n\n\n<li>Magnetizing current<em>,&nbsp;<\/em><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page517_2.png\" alt=\"img\" width=\"417\" height=\"41\">Under the given condition, transformer is operated at no-load.Where&nbsp;<em>V<\/em><sub>1<\/sub>&nbsp;= 230 V;&nbsp;<em>I<\/em><sub>0&nbsp;<\/sub>= 6.5 A;&nbsp;<em>I<\/em><sub>w&nbsp;<\/sub>= 1.0 A<em>I<\/em><sub>mag<\/sub>&nbsp;= 6.423 A;&nbsp;<em>E<\/em><sub>1<\/sub>&nbsp;= 230 V;&nbsp;<em>E<\/em><sub>2&nbsp;<\/sub>= 2300 V<\/li>\n<\/ol>\n\n\n\n<p id=\"para-253\"><strong>Example 10.10<\/strong><\/p>\n\n\n\n<p id=\"para-254\">The no-load current of a transformer is 5 A at 0.25 p.f. when supplied at 230 V, 50 Hz. The number of turns on primary winding are 200. Calculate (i) maximum value of flux in the core, (ii) core loss, (iii) magnetizing current, and (iv) exciting resistance and reactance of the transformer. Also draw its equivalent circuit<em>.<\/em><\/p>\n\n\n\n<p id=\"para-255\"><em>Solution:<\/em><\/p>\n\n\n\n<ol class=\"wp-block-list\" id=\"ol-014\">\n<li>Using the relation,&nbsp;<em>E<\/em><sub>1<\/sub>&nbsp;= 4.44<em>N<\/em><sub>1<\/sub><em>&nbsp;f \u0278<\/em><sub>m<\/sub>or&nbsp;230 = 4.44 \u00d7 220 \u00d7 50 \u00d7&nbsp;<em>\u0278<\/em><sub>m<\/sub>\u2234 Maximum value of flux&nbsp;<em>\u0278<\/em><sub>m<\/sub>&nbsp;= 518 m Wb<\/li>\n\n\n\n<li>Core loss,&nbsp;<em>P<\/em><sub>0<\/sub>&nbsp;=&nbsp;<em>V<\/em><sub>1<\/sub><em>I<\/em><sub>0<\/sub>&nbsp;cos&nbsp;<em>\u0278<\/em><sub>0<\/sub>&nbsp;= 230 \u00d7 5 \u00d7 0.25 = 287.5 W<\/li>\n\n\n\n<li>No-load p.f., cos&nbsp;<em>\u0278<\/em><sub>0<\/sub>&nbsp;= 0.25;sin&nbsp;<em>\u0278<\/em><sub>0<\/sub>&nbsp;= sin cos<sup>\u22121<\/sup>&nbsp;0.25 = 0.9682Magnetizing current component,&nbsp;<em>I<\/em><sub>m<\/sub>&nbsp;=&nbsp;<em>I<\/em><sub>0<\/sub>&nbsp;sin<em>\u0278<\/em><sub><\/sub><sub>0<\/sub>&nbsp;= 5 \u00d7 0.9682 = 4.84 AExciting resistance,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page517_3.png\" alt=\"img\" width=\"371\" height=\"67\">Exciting reactance,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page517_4.png\" alt=\"img\" width=\"272\" height=\"66\"><\/li>\n<\/ol>\n\n\n\n<p id=\"para-262\">The equivalent circuit is shown in\u00a0Figure 10.15. The values of different quantities are mentioned in the solution itself.<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page517_5.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-263\"><strong>Fig. 10.15<\/strong>&nbsp;&nbsp;Equivalent circuit of a transformer at no-load<\/p>\n\n\n\n<p id=\"para-264\"><a><\/a><strong>Example 10.11<\/strong><\/p>\n\n\n\n<p id=\"para-265\">At open circuit, transformer of 10 kVA, 500\/250 V, 50 Hz draws a power of 167 W at 0.745 A, 500 V. Determine the magnetizing current, watt-full current, no-load power factor, hysteresis angle of advance, equivalent resistance and reactance of exciting circuit referred to primary side<em>.<\/em><\/p>\n\n\n\n<p id=\"para-266\"><em>Solution:<\/em><\/p>\n\n\n\n<p id=\"para-267\">Here,<\/p>\n\n\n\n<p id=\"para-268\">&nbsp;<\/p>\n\n\n\n<p><em>V<\/em><sub>1&nbsp;<\/sub>= 500 V;&nbsp;<em>I<\/em><sub>0&nbsp;<\/sub>= 0.745 A;&nbsp;<em>P<\/em><sub>0&nbsp;<\/sub>= 167 W<\/p>\n\n\n\n<p id=\"para-269\">Watt-full component of current,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_1.png\" alt=\"img\" width=\"240\" height=\"66\"><\/p>\n\n\n\n<p id=\"para-270\">Magnetising component of current,&nbsp;<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_2.png\" alt=\"img\" width=\"152\" height=\"42\"><\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_3.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-271\">No-load power factor,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_4.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-272\">Hysteresis angle of advance,<\/p>\n\n\n\n<p id=\"para-273\">&nbsp;<\/p>\n\n\n\n<p><em>\u0278<\/em><sub>0<\/sub>&nbsp;= cos<sup>\u22121<\/sup>&nbsp;0.448 = 63.36\u00b0 lag<\/p>\n\n\n\n<p id=\"para-274\">Exciting resistance,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_5.png\" alt=\"img\"\/><\/figure>\n\n\n\n<p id=\"para-275\">Exciting reactance,<\/p>\n\n\n\n<figure class=\"wp-block-image\"><img decoding=\"async\" src=\"https:\/\/learning.oreilly.com\/api\/v2\/epubs\/urn:orm:book:9789332558311\/files\/images\/page518_6.png\" alt=\"img\"\/><\/figure>\n","protected":false},"excerpt":{"rendered":"<p>A transformer is said to be on no-load when secondary winding is open circuited and the secondary current&nbsp;I2&nbsp;is zero. In this case, neither the secondary winding has any effect on the magnetic flux in the core nor it has any effect on the primary current. In actual transformer, the losses cannot be neglected. Therefore, if [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":2841,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[413],"tags":[],"class_list":["post-2853","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-single-phase-transformers"],"jetpack_featured_media_url":"https:\/\/workhouse.sweetdishy.com\/wp-content\/uploads\/2024\/08\/power-transformer.png","_links":{"self":[{"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/posts\/2853","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/comments?post=2853"}],"version-history":[{"count":1,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/posts\/2853\/revisions"}],"predecessor-version":[{"id":2854,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/posts\/2853\/revisions\/2854"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/media\/2841"}],"wp:attachment":[{"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/media?parent=2853"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/categories?post=2853"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/workhouse.sweetdishy.com\/index.php\/wp-json\/wp\/v2\/tags?post=2853"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}